CVE-2022-30317

Description

Honeywell Experion LX through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0055, there is a Honeywell Experion LX Control Data Access (CDA) EpicMo protocol with unauthenticated functionality issue. The affected components are characterized as: Honeywell Control Data Access (CDA) EpicMo (55565/TCP). The potential impact is: Firmware manipulation, Denial of service. The Honeywell Experion LX Distributed Control System (DCS) utilizes the Control Data Access (CDA) EpicMo protocol (55565/TCP) for device diagnostics and maintenance purposes. This protocol does not have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocol in question. An attacker capable of invoking the protocols' functionalities could issue firmware download commands potentially allowing for firmware manipulation and reboot devices causing denial of service.

Severity
CRITICAL
CVSS v3
9.1
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H · source nvd
Exploit chance (EPSS)
0.940%
chance of exploitation in the next 30 days
higher than 61.5% of scored CVEs · 2026-11-17
CISA KEV
Not listed
Public exploit code
None public
Exploit references (NVD and CNA): 0
Metasploit modules: 0
Nuclei templates: 0

Weakness

Timeline

  1. 2022-08-31Published by the CNA15:22 UTC

The timeline shows what already happened. To be told when this CVE changes next, watch it from the API.

Affected products

Products listed as vulnerable. Upgrade to the version under "Fixed in", or a later one.

ProductVulnerable versionsFixed in
honeywell experion_lx_firmware

Products and versions as NVD and the vendor that published the CVE list them.

References

Get more CVE data from the API.

Free without a key or signup. Pro adds monitoring and higher limits: pricing.

Sources